Sign In | Join Free | My insurersguide.com |
|
Brand Name : Hosem
Model Number : A-P10S
Certification : CE, ISO9001, ISO14001
Place of Origin : Fuzhou, China
MOQ : 1Set
Price : USD3350 - USD4000.00
Supply Ability : 300Sets Per Month
Delivery Time : 25 Days
Packaging Details : Plastic Form Packing or Wooden Packing
Model : A-P10S
Genset Type : Soundproof & Waterproof
Rated Output : 9kVA / 7.2kW
Standby Output : 10kVA / 8kW
Voltage : 400 / 230V
Phase : 3Phase 4 Wires
Frequency : 50Hz (60Hz for Optional)
Current : 13A
Diesel Engine : Perkins 403A-11G1
No. of Cylinder : 3 Cylinders in Line
Engine Power : 9.5kW at 1500RPM
Alternator : Leroy Somer Model TAL-A40-C
Alternator Power : 13kVA / 10.4kW
Controller : ComAp MRS10
Supply standby power 10kVA diesel generator powered by Perkins diesel engine model 403A-11G1 and Leroy Somer alternator model TAL-A40-C. The 10kVA Perkins diesel generator use the ComAp brand controller model MRS10 with heavy-duty electric gauges.
Supply Scope of Three Phase 10kVA Perkins Diesel Generator:
1. Perkins diesel engine model 403A-11G1 standby power 9.5kW at 1500r/min.
2. Leroy Somer alternator model TAL-A40-C rated output at 13kVA / 10.4kW at 50Hz.
3. Control panel with ComAp MRS10 controller made in the Czech and heavy-duty electric gauges.
4. Water cooling system with radiator and fan.
5. Base frame with fuel tank capacity at 40Litres for continues running for more than 8hours at 100% load.
6. 3 pole circuit breaker with capacity at 32A for 10kVA Perkins diesel generator.
7. Soundproof and waterproof canopy with the noise level at 68dBA at 7 meters for optional.
8. Dampers for anti-vibration for diesel engine and alternator.
9. One of D.C. 12V free maintenance for starting of Perkins diesel engine.
10. Complete set of documents included diesel engine manual, alternator manual, control panel manual, and diesel generator manual.
Specification of the 10kVA Perkins Diesel Generator:
Generator Set Specification | ||
Model | A-P10 | |
Max. Power | kVA | 10 |
kW | 8 | |
Rate Power | kVA | 9 |
kW | 7.2 | |
Frequency | Hz | 50 |
Rate Voltage | V | 400/230 |
Rate Current | A | 13.0 |
Fuel Tank Capacity | L | 50 |
Dimension For Open-type Genset | mm | 1150 X 550 X 1200 |
Weight For Open-type Genset | kg | 352 |
Dimension For Soundproof Genset | mm | 1750 X 800 X 1150 |
Weight For Soundproof Generator | kg | 532 |
Noise Level for Soundproof Generator at 7M | dBA | 68 |
Battery for Starting | One of 60A Free Maintenance Battery |
Specification of Perkins Diesel Engine:
Engine Manufacturer | Perkins | |
Engine Brand | Perkins | |
Engine Model | 403D-11G | |
No. of Cylinder | 3 Cylinder in line | |
Aspiration | Naturally Aspirated | |
Governor | Mechanical | |
Engine Max. Output Power | kW | 9.5 |
Displacement | L | 1.1 |
Compression Ratio | 23 : 1 | |
Starting Voltage | V | 12 |
Bore | mm | 77 |
Stroke | mm | 81 |
Lubrication Oil Capacity | L | 4.4 |
Intake Air Flow | M3/Min | 0.7 |
Fuel Consumption at 100% Load | L/H | 2.6 |
Specification of Leroy Somer Alternator:
Alternator Manufacturer | Leroy Somer | |
Alternator Model | TAL-A40-C | |
Alternator Brand | Leroy Somer | |
Rate Output | kVA | 13 |
Frequency | Hz | 50Hz |
Altitude | M | ≤1000 |
Insulation | Class H | |
Phase | 3 Phase | |
Working Temperature without power decrease | ≤40℃ | |
Working Altitude without power decrease | ≤1000m | |
Automatic Voltage Regulation | R205 | |
Protection Grade | IP23 | |
Alternator for optional | Stamford, Marathon, Mecc Alte and Hosem Brushless alternator for optional | |
Specification of Control Panel:
Controller Brand | ComAp | |
Controller Model | MRS10 | |
Breaker Brand | Delixi | |
Breaker Capacity (A) | 32 | |
Battery Charger | Smartgen Model BAC06A | |
Emergency Stop Button | Supply | |
Automatic Mains Fail (AMF) | Supply | |
Fuel Level | Supply | |
Automatic Transfer Switch | ATS as optional part | |
The control panel supply the full protection with alarm and shutdown of the diesel generator include Start-up fault (generator set shutdown), High coolant temperature (alarm and generator set shutdown), Low oil pressure (alarm and generator set shutdown), Low fuel level (alarm), Low cooling fluid level alarm (as optional), Overload (alarm and generator set shutdown), Battery voltage high (alarm). | ||
Optional controller: Each model of Deepsea, Smartgen, ComAp brand controller. |
Spare Parts of diesel engine included Cummins, Perkins, Deutz, Volvo, Doosan, SDEC, Yuchai Ricardo and other famous brand diesel engine are available in Fuzhou Hosem Power Co., Ltd.
![]() |